Product Name | Active Power Filter | Phase | 3 Phase 3 Wire,3 Phase 4 Wire |
---|---|---|---|
Usage | Steel, Metallurgy, Petrochemical, Railway, Wind Power | Function | Harmonic Management |
Frequency | 50/60hz | Rated Voltage | AC 400V 660V |
High Light | Active Power Filter 480a,Harmonic management Active Power Filter |
Applying world advanced power component
The world advanced IGBT component is applied, and the main circuit is a bridge full-control type PWM converter, which is featured by high power density and high reliability.
Digital control system
DSP high-speed detection and computation is employed, to ensure precise and effective current detection and compensation control; full digital control system is applied, so that the entire control process is realized by the software, to make the entire control system simpler and more reliable.
Monitoring and display system
Intelligent monitoring and display system is applied for flexible operation of the devices, with the operation parameters and working condition displayed clearly, the function of fault self-diagnosis and telecommunication interface for real-time communication with the host computer.
Unique group control system
SIKES is the first APF manufacturer in China that combines both active technology and passive technology to realize an intelligent control system using the active module to control the switching of the passive module, namely an integrated control system, to ensure the reliable operation of the equipment to the most extent.
Description | APF series | APF4 series |
Single module capacity | 25A , 50A , 100A | |
Capacity of the complete machine | 100A , 150A , 200A , 250A , 300A , 400A , 500A | |
Power supply voltage | 400x (l±20%) V or 660x (l±20%) V | |
Power supply frequency | 50x (l±10%) Hz | |
The number of harmonics can be filtered out | 2 times~61 times (eliminate all harmonics or specified harmonics ) | |
Filtering number setting | Individual setting for each harmonic wave is allowed | |
Efficiency | Reaching up to 98% | |
Neutral line filtering capability | — | One to three times of the phase line harmonic current |
Total response time | £10ms | |
Compensation mode | Harmonic compensation, reactive power compensation or harmonic compensation and reactive power compensation conducted simultaneously | |
Parallel operation capacity | Up to 10 sets of complete machines | |
Active power loss | 3% rated output capacity | |
Display function (User Interface) |
1. Power; power factor; voltage and current value, total current distortion rate, spectrum diagram, current waveform
3. Operation mode setting, dry node setting, fault information and operation time inquiry |
|
Protection method | Input over-voltage, input phase dislocation/loss, over-current, over-heat over-voltage/under-voltage of DC bus and automatic current limiting protection of overload | |
Cooling mode | Forced air cooling | |
Protection grade | IP20/IP52, (higher protection class can be customized) | |
Color | RAL7035 | |
Direction of incoming line | U pwa rd/d ownwa rd | |
Installation environment | Indoor installation; recommended altitude for installation shall not exceed 1000m (use with reduced capacity for high altitude) | |
Dimensions WxDxH(mm) | Module: 442x425x88(25A), 440x609x222(50A,100A) FCL: 800x800x2200 | |
Module weight | 10kg(25A),30kg(50A),40kg(100A) | |
Ambient temperature | Operating temperature: -25°C~50°C (use with reduced capacity for higher ambient temperature) Storage temperature: -40°C~60°C | |
Communication | Remote RS485 Ethernet communication function (optional), and upper computer monitoring software (optional) | |
Scope of application | Applied to the power grid system with neutral three-phase balance in industrial field, and can filter non-zero sequence harmonics and compensate reactive power | Applied to three-phase systems with neutral lines and can filter out harmonics flowing through the phase lines and neutral lines at the same time |